Hei alle sammen,
eg har et oppsett for å lese ut en del verdier via modbus på mitt Villavent / Systemair VTR150. Det er tilkoblet via en modbus-til-ethernet converter. I min konfigurasjon har eg følgende innlesing:
modbus:
- name: vtr150
type: tcp
host: 10.160.1.98
port: 8234
timeout: 3
delay: 5
close_comm_on_error: false
retry_on_empty: true
retries: 10
sensors:
- name: Utetemperatur
unit_of_measurement: °C
scale: 0.1
precision: 1
scan_interval: 10
slave: 1
address: 12101
data_type: int
device_class: temperature
- name: Tilførselsluft
unit_of_measurement: °C
scale: 0.1
precision: 1
scan_interval: 10
slave: 1
address: 12102
data_type: int
device_class: temperature
- name: Utluft
unit_of_measurement: °C
precision: 1
scan_interval: 10
slave: 1
address: 12543
data_type: int
device_class: temperature
- name: Luftfuktighet
unit_of_measurement: "%"
scale: 1
precision: 1
scan_interval: 10
slave: 1
address: 12135
data_type: int
device_class: humidity
- name: RH-sensor
unit_of_measurement: "%"
scale: 1
precision: 1
scan_interval: 10
slave: 1
address: 1000
data_type: int
device_class: humidity
- name: Viftemodus
slave: 1
address: 1130
precision: 0
count: 1
data_type: uint
Mitt problem er at verdien "Utluft" blir vist som 210 grader C når den skulle vere 21 grader C. Altså en type konverteringsfeil. Korleis kan eg få endra dette i konfigurasjonen eller før dataene sendes til via Homebridge til IOS?